Description
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Rated current | < 20 mA | |
Input | ||
Connection side | field side | |
Connection | terminals 4+, 5- | |
Input resistance | min. 10 MΩ | |
Transmission range | 0 ... 12 V | |
Offset voltage/current | < 2 mV / < 7 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage | 0 ... 12 V | |
Output resistance | max. 20 Ω | |
Transfer characteristics | ||
Cut-off frequency | 1.2 kHz (-3 dB) | |
Deviation | ||
After calibration | ± 5 mV at 20 °C (68 °F) | |
Influence of ambient temperature | ≤ 0.005 % of range per K | |
Rise time | ≤ 0.4 ms | |
Galvanic isolation | ||
Output/power supply | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BAS 01 ATEX 7262 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2] | |
Voltage | 18 V | |
Current | 4.2 mA | |
Power | 19 mW | |
Supply | ||
Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) | |
Output | ||
Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) | |
Certificate | BASEEFA 10 ATEX 0079X | |
Marking | II 3G Ex ec IIC T4 Gc [device in zone 2] | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 10.0040X | |
IECEx marking | Ex ec IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210120 |
ECLASS 10.0.1 | 27210120 |
ECLASS 9.0 | 27210120 |
ECLASS 8.0 | 27210120 |
ECLASS 5.1 | 27210120 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |