Description
General specifications | ||
---|---|---|
Signal type | Analog input/analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Rated voltage | < 30 V DC , loop powered | |
Power dissipation | 0.2 W | |
Control circuit | ||
Connection | terminals 8-, 9+ | |
Voltage | max. 30 V DC | |
Current | 4 ... 20 mA (quiescent current < 0.5 mA) | |
Power dissipation | 150 mW at 20 mA and Uin < 24 V | |
Field circuit | ||
Connection | terminals 1+, 2 / 3- | |
Voltage | ≥ 16 V for supply voltage > 21 V | |
Current | 4 ... 20 mA (linear transmission 1 ... 22 mA) | |
Load | ≤ 800 Ω (at 20 mA) | |
Transfer characteristics | ||
Voltage drop | see note | |
Deviation | ||
After calibration | ≤ ± 80 µA linearity, load and voltage dependence at 20 °C (68 °F) | |
Influence of ambient temperature | < 0.5 µA/K | |
Damping | approx. 3 dB | |
Rise time | ≤ 20 µs at 0 Ω, ≤ 600 µs with 800 Ω load | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 02 ATEX 2064 | |
Marking | II (2)G [EEx ib] IIC | |
Voltage | 23.1 V DC | |
Current | 28 mA | |
Power | 0.647 W | |
Supply | ||
Maximum safe voltage | 253 V (Attention! The rated voltage can be lower.) | |
Certificate | PF 11 CERT 0902 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | device with FM approval on request | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210120 |
ECLASS 10.0.1 | 27210120 |
ECLASS 9.0 | 27210120 |
ECLASS 8.0 | 27210120 |
ECLASS 5.1 | 27210120 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |