Description
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Systematic capability (SC) | SC 3 | |
Performance level (PL) | PL e | |
Supply | ||
Connection | loop powered | |
Rated voltage | 19 ... 30 V DC loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | Input terminals 7, 8 ; test input terminals 9, 10, 11, 12 | |
Pulse/Pause ratio | 150 ms / 150 ms | |
Test pulse length | max. 4 ms from DO card | |
Test input | see functional safety manual | |
Signal level |
0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V |
|
Rated current |
0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
|
Output | ||
Connection side | field side | |
Connection | terminals 4, 5, 6 | |
Contact loading |
253 V AC/5 A/cos φ 0.7; 30 V DC/5 A resistive load 253 V AC / 1/2 HP |
|
Minimum switch current | 10 mA / 24 V DC | |
Energized/De-energized delay | 150 ms / 150 ms | |
Mechanical life | 5 x 106 switching cycles | |
Fuse rating |
2.5 A (scope of delivery) max. 5 AT, recommended maximum utilization of the fuse: 80 % |
|
Transfer characteristics | ||
Switching frequency | < 3 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Machinery Directive | ||
Directive 2006/42/EC | EN IEC 62061:2021 , EN/ISO 13849-1:2015 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
|
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 15 CERT 3933 X | |
Marking | II 3G Ex nC ec IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210101 |
ECLASS 10.0.1 | 27210101 |
ECLASS 9.0 | 27210101 |
ECLASS 8.0 | 27210101 |
ECLASS 5.1 | 27210121 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121543 |